GEEntellisys™ Low Voltage SwitchgearIntegrator’s Guide
Integrator’s Guide101.1.5 Supported function codesModbus officially defines function codes from 1 to 127 though only a small subset is generally neede
Modbus® protocol implementation 111.1.5.2 Function Code 05H – Execute OperationThis function code allows the master to perform various operations in t
Integrator’s Guide12SLAVE RESPONSEPACKET FORMAT EXAMPLE (HEX)SLAVE ADDRESS 11FUNCTION CODE 05OPERATION CODE - hi 00OPERATION CODE - lo 01CODE VALUE -
Modbus® protocol implementation 131.1.5.3 Function Code 06H – Store Single SettingThis function code allows the master to modify the contents of a sin
Integrator’s Guide141.1.5.4 Function Code 10H – Store Multiple SettingsThis function code allows the master to modify the contents of a one or more co
Modbus® protocol implementation 151.1.5.5 Exception responsesProgramming or operation errors usually happen because of illegal data in a packet. These
Integrator’s Guide161.1.6 File transfers1.1.6.1 Obtaining CPU files using Modbus protocolThe CPU has a generic file transfer facility, meaning that yo
Modbus® protocol implementation 171.1.6.2 Modbus password operationThe COMMAND password is set up at memory location 0458h. Storing a value of “0” rem
Integrator’s Guide181.2 Interfacing to the Alarm HandlerThe set of registers beginning at 0648h provides the means to interface to each CPU’s Alarm Ha
19 Modbus Memory Map NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the Range and/or Step imply a greate
DEH-232Warnings, Cautions, and Notes as used in this publicationWarningsWARNING! Warning notices are used in this publication to emphasize that hazard
20 Communications (Read/Write Setting) 0210 External Ethernet IP Address 0 to 4294967295--- 1 F003 3232235876 0212 External Ethernet IP Subnet Ma
21 Demand (Read/Write Command) 0506 Demand Reset All Command 0 to 1 --- 1 F126 0 (No) Demand (Read Only) 0507 Number Of Demand Reset
22 Hardware Information (Read Only) 053D Flash Lifetime 1 to 10 --- 1 F001 1 Source Vectors (Read/Write Setting) 0600 Expected Nodes x State 0 to
23 0678 Overfrequency Alarm State 0 to 4294967295--- 1 F722 0 067A Overfrequency Alarm Ack 0 to 4294967295--- 1 F722 0 067C High Resistance G
24 06D2 Breaker Mechanical Life 100 Ack 0 to 4294967295--- 1 F722 0 06D4 Bus Differential Trip Alarm State 0 to 4294967295--- 1 F722 0 06D6 B
25 1364 ...Repeated for module number 15 13A2 ...Repeated for module number 16 13E0 ...Repeated for module number 17 141E ...Repeated for module numbe
26 1B1E ...Repeated for module number 22 1B44 ...Repeated for module number 23 1B6A ...Repeated for module number 24 1B90 ...Repeated for module numbe
27 1EC0 ...Repeated for module number 15 1EE0 ...Repeated for module number 16 1F00 ...Repeated for module number 17 1F20 ...Repeated for module numbe
28 2130 ...Repeated for module number 2 2160 ...Repeated for module number 3 2190 ...Repeated for module number 4 21C0 ...Repeated for module number 5
29 26C0 ...Repeated for module number 3 26D0 ...Repeated for module number 4 26E0 ...Repeated for module number 5 26F0 ...Repeated for module number 6
How to contact usPlease have your Entellisys System Summary # and Sub # ready when calling. This information can be found on the Entellisys HMI on the
30 28F7 ...Repeated for module number 8 2908 ...Repeated for module number 9 2919 ...Repeated for module number 10 292A ...Repeated for module number
31 2ACE ...Repeated for module number 2 2B1C ...Repeated for module number 3 2B6A ...Repeated for module number 4 2BB8 ...Repeated for module number 5
32 Source Demand (Read Only) (30 modules) 35BA SRC x Demand Log Records Since Last Clear 0 to 4294967295--- 1 F003 0 35BC SRC x Demand Log In
33 500B SRC x Product Type 0 to 2 --- 1 F716 0 (Low Voltage Switchgear) 500C SRC x NodeProt Rating Switch 0 to 65535 --- 1 F001 0 500D SRC x N
34 5768 ...Repeated for module number 25 57B7 ...Repeated for module number 26 5806 ...Repeated for module number 27 5855 ...Repeated for module numbe
35 5CB0 SRC x OV Trip Time Delay 0.5 to 600 --- 0.5 F001 300 5CB1 SRC x OV Trip Phase Requirement 1 to 3 --- 1 F001 1 5CB2 SRC x OV Trip Open
36 5CE7 SRC x Time Date Initial Energization 0 to 4294967295--- 1 F050 0 Source Settings (Read Only) (30 modules) 5CE9 SRC_X_Breaker_Service_
37 6644 ...Repeated for module number 16 66EA ...Repeated for module number 17 6790 ...Repeated for module number 18 6836 ...Repeated for module numbe
38 73B6 ...Repeated for module number 20 73E8 ...Repeated for module number 21 741A ...Repeated for module number 22 744C ...Repeated for module numbe
39 Force Contact Inputs (Read/Write Setting) 8700 Force Contact Input x State (128 items) 0 to 2 --- 1 F144 0 (Disabled) Force Contact Outputs (Re
40 AC06 ...Repeated for module number 7 AC07 ...Repeated for module number 8 AC08 ...Repeated for module number 9 AC09 ...Repeated for module number 1
41 B405 Breaker Control x Lockout 0 to 65535 --- 1 F300 0 B406 Breaker Control x Lockout Reset 0 to 65535 --- 1 F300 0 B407 Reserved (18 item
42 ZSI ST Tier Settings (Read/Write Setting) (30 modules) B7C2 SRC x ST ZSI Zone 1 Tier Settings (16 items) 0 to 3 --- 1 F733 0 (ZSI Tier 0) B7D2
43 C212 ...Repeated for module number 4 C262 ...Repeated for module number 5 C2B2 ...Repeated for module number 6 C302 ...Repeated for module number 7
44 CC12 Zone x MSGF Alarm I2T Curve (16 items) 0 to 1 --- 1 F102 0 (Disabled) CC22 Zone x MSGF Trip Enabled (16 items) 0 to 1 --- 1 F102 0 (Di
45 Setting (16 items) D252 Zone x Summation MSGF Trip or Open 0 to 1 --- 1 F727 0 (Open and don't activate lockout) D253 Zone x Summation Res
46 D4D4 ...Repeated for module number 17 D4EE ...Repeated for module number 18 D508 ...Repeated for module number 19 D522 ...Repeated for module numbe
47 D918 ...Repeated for module number 59 D932 ...Repeated for module number 60 D94C ...Repeated for module number 61 D966 ...Repeated for module numbe
48 DD5C ...Repeated for module number 101 DD76 ...Repeated for module number 102 DD90 ...Repeated for module number 103 DDAA ...Repeated for module nu
49 E160 ...Repeated for module number 11 E17E ...Repeated for module number 12 E19C ...Repeated for module number 13 E1BA ...Repeated for module numbe
Contents 51 Integrator’s Guide1.1 Modbus® protocol implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50 E64C ...Repeated for module number 53 E66A ...Repeated for module number 54 E688 ...Repeated for module number 55 E6A6 ...Repeated for module numbe
51 EB38 ...Repeated for module number 95 EB56 ...Repeated for module number 96 EB74 ...Repeated for module number 97 EB92 ...Repeated for module numbe
52 EFBE ...Repeated for module number 7 EFD5 ...Repeated for module number 8 EFEC ...Repeated for module number 9 F003 ...Repeated for module number 1
53 F384 ...Repeated for module number 49 F39B ...Repeated for module number 50 F3B2 ...Repeated for module number 51 F3C9 ...Repeated for module numbe
54 F74A ...Repeated for module number 91 F761 ...Repeated for module number 92 F778 ...Repeated for module number 93 F78F ...Repeated for module numbe
55 Virtual Inputs (Read/Write Setting) (32 modules) FAB4 Virtual Input x Function 0 to 1 --- 1 F102 0 (Disabled) FAB5 Virtual Input x Nam
56 Modbus Memory Map Format Codes Format Name Format Type/Bitmask Format Definition F001 UINT16 UNSIGNED 16 BIT INTEGER F003 UINT32 UNSIGN
57 F203 TEXT16 16 CHARACTER ASCII TEXT F204 TEXT80 80 CHARACTER ASCII TEXT F205 TEXT12 12 CHARACTER ASCII TEXT F300 UINT16 FLEXLOGIC BASE TYPE
58 6 IButton Missing 7 EEPROM Configuration Invalid 8 Not Used 9 Not Used 10 Not Used 11 Not Used 12 Not Used 13 Not U
59 7 Not Used 8 Not Used 9 Control_Power1_Status 10 Control_Power2_Status 11 App Flash CRC Fail 12 Boot Flash CRC Fail 13 Option Bo
6 Contents
60 8 Start Firmware Download 9 Switch Firmware 10 Cancel Firmware Download 11 Ignore CPU Message 12 Firmware Packet Present 13
61 1 BAND 2 2 BAND 3 3 BAND 4 4 BAND 5 5 BAND 6 6 BAND 7 F714 ENUMERATION SRCx Ground Fault Protection or Alarm Select 0
62 21 Bit field representing a 0 or 1 for Node 21 22 Bit field representing a 0 or 1 for Node 22 23 Bit field representing a 0 or 1 for No
63 10 10 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 11 11 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
64 29 61 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 30 62 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
Modbus® protocol implementation 71 Integrator’s Guide1.1 Modbus® protocol implementation1.1.1 IntroductionThe CPU supports a number of communications
Integrator’s Guide81.1.3 Data link layerCommunications takes place in packets, which are groups of asynchronously framed byte data. The master transmi
Modbus® protocol implementation 91.1.4 CRC-16 AlgorithmThe CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and