Section Topic
1 Thanks - DEH40657
2 Installation and Start-up Instructions for AF-650 Bypass, NON Bypass & Disconnect Drive Panels
- DEH40650
3 Operating and Troubleshooting Instructions for AF-650 GP Bypass Panels - DEH40652
4 Operating and Troubleshooting Instructions for AF-650 GP NON Bypass & Disconnect Drive
Panels - DEH40658
5 AF-650 GP User’s Guide (DET – 607 or DET 608) DEH40655
6 Appendix A Current Ratings and Fuse Sizes - DEH40654
7 In-Warranty Information Form DEH40656
8 Appendix B Wire Sizes, Torque and Estimated Watt loss Details DEH40653
9 Product Drawings Electrical and Mechanical
DEH40651 Page 1 AN 12-1007 Rev 04, 04/04/2012
Table of Contents
Vue de la page 0
1 2 3 4 5 6 ... 56 57

Résumé du contenu

Page 1 - Table of Contents

1 Section Topic 1 Thanks - DEH40657 2 Installation and Start-up Instructions for AF-650 Bypass, NON Bypass & Disconnect

Page 2

10 1. Operator Devices Your Bypass panel is equipped with several panel door mounted operator devices, which may include the following: one (1)

Page 3

11 In the “Test” position AC input power to the drive will be applied and the inverter will run at the speed set in using the Hand/Off/Aut

Page 4

12 Hand/Off/Auto Selector This selector is also referred to as the H-O-A switch. In the “Off” position power will be removed from the m

Page 5

13 Harmonic Filter When the panel is provided with the Harmonic filter, Make sure to set the timer (CITMR) based on motor starting characteristic

Page 6

14 due to a fault and the panel is configured with the optional automatic bypass functionality. Note, included with the optional automatic bypass

Page 7

15 2. Customer Terminal Board – “CTB” Inside the panel enclosure there is terminal board for convenient connection of customer control wiring. T

Page 8 - AF 650 GP BYPASS PANELS

16 CTB1-8 through CTB1-9 Drive Program Jumper. These positions come with a jumper from the factory to allow testing of the drive with the Test/Is

Page 9

17 minimal time delay of 10 seconds is necessary by the operator prior to closing the remote bypass contacts and bypassing the drive. DO NOT jumpe

Page 10 - 1. Operator Devices

18 3. AF 650 GP Drive Terminal Board I/O Any of the AF 650 GP terminal board I/O points which are not already in use for proper operation of the

Page 11

19 4. Adjustments The AF 650 GP & Bypass panel has several user settable adjustments, which allow it to be tailored specifically for your 3-p

Page 12

2 GE Drives wishes to thank you for choosing our adjustable frequency controller product. We are committed to being the world’s leading supplier o

Page 13

20 coordination issues. Therefore if it is necessary to change the input fuses, please consult your preferred fuse supplier and/or your local GE s

Page 14

21 is to provide continuous long term overload protection against loads which draw current in excess of the motor’s rating. According to GE ED

Page 15

22 1. Allow the OL to cool sufficiently between restarts. There is typically a 4 to 1 difference between the operation time of the OLs in their c

Page 16

23 5. AF 650 GP Drive Function Code Changes The AF 650 GP Adjustable Frequency Drive has programmable function. A complete description of these f

Page 17

24 AN – 0 # OK AN – 00 TIME [Loss of ref time] 10 Sec – Default AN – 01 – TIME OUT FUNCTION [3] Jogging Jog frequency setup Main Menu Para

Page 18

25 Ok Downward arrow E-05 = [7] External interlock (Terminal 33 on drive (Digital I/P)) Auto-Tune In the event that it is desired to “auto-tune”

Page 19 - 4. Adjustments

26 6. Troubleshooting Drive and Bypass Motor Rotation If careful attention to phase rotation is not made during connection of the panel to the t

Page 20

27 Your AF-650 GP Non-Bypass & Disconnect Drive Panels comes with an AF-650 GP Adjustable Frequency Drive from GE Drives mounted on or in

Page 21

28 1. Operator Devices page 3 2. Customer Terminal Board page 5 3. AF-650 GP Drive Terminal Board I/O

Page 22

29 1. Operator Devices Operator Devices for Disconnect Drive – The following section does not apply to the Disconnect Drive Panels. All door moun

Page 23

3 The following information is provided for reference use during the installation of your AF-650 GP Bypass, Non-Bypass & Disconnect Drive P

Page 24

30 Hand - Off - Auto on Drive Keypad All AF-650 GP Drive Panels include a keypad for programming and operation of the drive and includes Hand, Off,

Page 25

31 2. Customer Terminal Board – “CTB” The following section does not apply to the Disconnect Drive Panels. All customer terminations

Page 26 - 6. Troubleshooting

32 CTB1-18 through CTB1-19 HOA – Auto status for customer CTB1-20 through CTB1-22 Analog Speed Reference Input. Connect customer supplied 0-10

Page 27

33 3. AF-650GP Drive Terminal Board I/O CTB-Customer Terminal Boards are not available in Disconnect Drive panels Any of the AF 650 GP terminal b

Page 28

34 4. Adjustments The AF-650 GP panel has several user settable adjustments which allow it to be tailored specifically for your 3-phase induction

Page 29

35 Because instantaneous trip circuit breakers are so fast acting, the NEC actually allows trip level settings up to 1300% of motor FLA if it can b

Page 30

36 5. AF-650 GP Drive Function Code Changes The following section does not apply to the Disconnect Drive Panels. All programmable functions are a

Page 31

37 AN - ## OK AN – 0 # OK AN – 00 TIME [Loss of ref time] 10 Sec – Default AN – 01 – TIME OUT FUNCTION [3] Jogging Jog frequency setup Ma

Page 32

38 E-0# Ok Downward arrow E-05 = [7] External interlock (Terminal 33 on drive (Digital I/P))

Page 33

39 6. Troubleshooting Auto-Tune In the event that it is desired to “auto-tune” the drive to the connected motor, reference the following instructi

Page 34

4 The environments for NEMA Type 1 enclosures shall be indoor where the following condition may exist; falling dirt. The environments

Page 35

40 AF-650 GP User’s Guide DET -607 AF 650 GP User’s Guide for up to 50HP @ 208V & up to 100HP @460/575 or DET - 608 AF 650 G

Page 36

41 Table A 208 VAC Panel Current Ratings and Maximum Allowable Fuse Sizes Table B 460 VAC Panel Current Ratings and Maximum Allowable Fus

Page 37

42 Table A AF 650 GP Panels – 208 VAC Current Ratings and Maximum Fuse Sizes VAC Panel VAC Panel Max Allowable Hp Rating Current Rat

Page 38

43 Table B AF 650 GP Panels – 460 VAC Current Ratings and Maximum Fuse Sizes VAC Panel VAC Panel Max Allowable Hp Rating Current Rat

Page 39

44 Table C AF 650 GP Panels – 575 VAC Current Ratings and Maximum Fuse Sizes VAC Panel VAC Panel Max Allowable Hp Rating Current Rat

Page 40

45 In-Warranty Information Form The purpose of this form is to provide specific information to GE Drives to aid in expediting par

Page 41

46 VI. To aid in part replacement please fill complete the following: To: ______________________ From: _____________________ Fax: _________

Page 42

47 DEH40653 – Page 1

Page 43

48 Table – 1 (208V) Device AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque NON FUSED DISCONNECTOR AND FUSE BLOCK 2-5 # 14

Page 44

49 Table – 2 (460V) Device AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque NON FUSED DISCONNECTOR AND FUSE BLOCK 1 throu

Page 45 - V. Description Of Failure:

5 No conduit holes are provided in the enclosure; therefore the customer must install all conduit holes. Place a protective covering over

Page 46

50 Table – 2 (460V) Device AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque Load Reactor (6KFP Series) 1 through 5 # 22

Page 47 - Details

51 Table – 3 (575V) Device AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque NON FUSED DISCONNECTOR AND FUSE BLOCK 1 throu

Page 48

52 Table – 3 (575V) Device AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque Load Reactor (6KFP Series) 1 through 5 # 22

Page 49

53 UL508 Table 54.1 , Tightening torque for screws Test wire size installed in connector (AWG) Tightening torque (lb in.) Slotted head no 10 and la

Page 50

54 DEH40653 – Page 8

Page 51

55 Table A DEH40653 – Page 9

Page 52

56 Table B 6KGP Series Non-Bypass Configuration - Industrial Channel HP Ratings Estimated Watt Loss(Watts) at 208V 460V 575V 2 225 181 187 3 266

Page 53

57 Table C 6KGP*L Series Non-Bypass Configuration - Industrial Channel HP Ratings Estimated Watt Loss (Watts) at 208V 460V 575V 2 71 68 71 3 101

Page 54

6 with load reactor), contactor (non-bypass panel with load contactor) or overload relay (all Bypass contactor configurations). For drive panels o

Page 55 - Industrial

7 Avoid routing signal wiring with power wiring. If signal wiring is routed with control wiring a minimum separation of one (1) inch

Page 56

8 Your AF 650 GP Bypass Panel comes with an AF 650 GP Adjustable Frequency Drive from GE Drives mounted on or in an enclosure which contains t

Page 57

9 1. Operator Devices page 3 2. Customer Terminal Board page 8 3. AF 650 GP Drive Terminal Board I/O