DEH40152
DEH40152 Rev.No.02
1
g A-Series
®
II Panelboards
AD/AE/AQ Type P & N Power Panel
TQD Three-Phase Circuit Breaker
Kits
Introduction
These instructions describe the installation of TQD three-phase circuit breaker kit into an
A-Series
®
II panelboard. These kits are for use in panelboards ordered with Un-Specified
Space. The catalog number for six-pole TQD breaker kit is ASPP6QD6D
Parts List for ASPP6QD6D Table 1.
ITEM # DESCRIPTION PART # QTY
1 BRANCH BASE FOR B PHASE 139C5702BQDG1 1
2 BRANCH BASE FOR A PHASE 139C5702AQDG1 1
3 BRANCH BASE FOR C PHASE 139C5702CQDG1 1
4 (SPOOL) 315A7036P19 6
5 (SCREW-SPOOL) 315A7037P4 6
6 (WASHER-SPOOL) 75A105503P111 6
7 (SCREW-BUS) 315A7034P8 6
8 3P BRACKET 139C5500P81 2
9 SCREW, BKT TO RAIL N667P16008B6 8
10 SCREW, C/B TO BKT N80P150046B6 4
11 FILLER PLATE, TQD 139C5503P64 1
12 SCREWS , #10-32 X 3/8 N722P16006B6 4
13 NUT N210P16B6 6
14 CUP WASHER 254V644P1 4
Installation
WARNING: Before attempting to install one of these kits, remove all power from the
panelboard.
Use the following procedure to install a TQD circuit breaker kit. Call-out numbers in the
illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1.
Installation of a three-pole kit is illustrated in Figure 1.
1. Remove the interior assembly from its packaging and verify that all parts are
present, as given in the parts list.
2. Remove the 8 screws (600A and 800A panels) securing the dead front to
panelboard interior. Lift off the dead front and place it and the screws aside.
3. Remove the circuit breaker kit from its packaging and verify that all parts are
present, as given in the packing list.
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - II Panelboards

DEH40152 DEH40152 Rev.No.02 1g A-Series ® II Panelboards AD/AE/AQ Type P & N Power Panel TQD Three-Phase Circuit Breaker Kits Intro

Page 2

DEH40152 DEH40152 Rev.No.02 24. Refer Fig.no.1 to mount the breaker on interior. Place branch base for A phase [2] adjacent to crossbar [15] as sho

Page 3

DEH40152 DEH40152 Rev.No.02 38. Insert two screws [10] into the holes in the circuit breaker and tighten to bracket [8] with 18-22 in-lb. 9. Remov

Page 4

DEH40152 DEH40152 Rev.No.02 4 Figure 3. Attaching the shield insert to the shield for TQD breaker installation in A-Series® II Panelb

Page 5 - SF/TFJ 1.875

DEH40152 DEH40152 Rev.No.02 5 Figure 4. Distance between breakers Table 2. Distance between breakers.

Page 6

DEH40152 DEH40152 Rev.No.02 6 Figure 5 Distance between the Crossbar and TQD breaker These instructions do not cover all details or variations in